RIG
RAT II
The
stainless steel RIG RAT II is state-of-the-art in gas detection,
detecting for combustibles, toxics and/or oxygen hazards. With
independent wireless radio signal transmission the self-powered,
solar capable detectors provide the ultimate in flexibility and
versatility.
Rig
Rat II is totally modular in design with plug-in ports for
all field interfaces: remote sensors, remote alarms, relays,
solar power, etc.
Microprocessor
based operation and forefront sensor technology assures
reliability and performance.
Eliminate
Signal and Power Lines:
Signals are transmitted
via coded radio channels and each unit in the system is
independently powered. Cut installation costs up to 75% by
eliminating the cost of cabling, wiring, conduit and trenching.
System components, Detectors, Sensors, Controllers, Remote
Alarms, Relays, etc. are all independent of signal and power
lines.
|
|
|
|
|
 |
 |
 |
 |
 |
 |
 |
|
|
Some
Typical Applications:
|
|
|
|
|
|
Field
Tough:
Rig
Rat
II provides field proven performance in extreme conditions from
the arctic to the desert.
Easy
Installation:
Installed
and operating by your field personnel in approximately 30 minutes.
Equipped with a rugged weatherproof stainless steel
enclosure and built-in mounting flanges, simply mount the
Detector to the wall and supply power.
Facility
Monitoring: Multi-point
systems can be expanded to 1000 or more individual monitoring
points with each Detector coded to a separate channel.
Perimeter
Monitoring: Provides
the most cost-effective solution to perimeter monitoring.
Portable
Monitoring: The only
portable, multi-point monitoring system in the world.
Field-proven on mobile work sites such as drilling/service rigs
and disaster response teams.
Detector
Sub-Site Controller:
The
Detector may activate remote relays and a solenoid driver to
control Emergency Shutdown Devices (ESD), building ventilation
systems and other field interfaces plus remote audible/visual
alarms.
|
|
|
|
|
|
FEATURES |
|
|
|
|
-
Independent
Power and Radio signal transmission
-
Microprocessor
operation ensures Performance and Reliability
-
Eliminates
wiring, cabling, conduit and trenching costs
-
Power
Choices: Battery, Solar, 24 VDC, 110/220 VAC
-
Signal
transmission up to 4 miles (6.5 km)
-
Simple,
straight forward, user-friendly operation
-
Modular
engineered design
-
Status
Panel advises all Features and Functions
-
Readouts
for each sensor (ppm, %)
-
Remote
Sensors and Options have plug-in ports
-
Dual
Alarm Levels for each Sensor (user adjustable)
-
Built-in
Audible and Visual Alarms
-
Change
the Gas monitored or Measuring Range any time in the field
-
Security
Key Access
-
Approved
intrinsically safe for use in: Class I, Div. 1, Groups C, D
Class II, Div. 1, Group G
-
Rugged
Stainless Steel self-contained enclosure
|
|
|
|
|
|
 |
Compatible
plug-in components make it easy to customize each detection
point. The Detector can easily be re-configured as your needs
change and grow. |
|
|
|
|
|
|
|
|
 |
GAS
DETECTORS
Equip the Detector with
one or two remote sensor heads in any combination desired and
change sensor or measuring range at ant time. A plug-in Logic
Block that is matched to the sensor configures the Detector and
LCD to the sensor and measuring range selected.
Detector
Components
1.
Carrying Handle
2. Mounting Bracket
3. Antenna port
4. Security Keylock
5. External Latch
6. Audible Alarm
7. Charger Port
8. Gas Label Bars
9. Option Ports (two)
10. LCD Display Panel
11. Sensor Ports (two)
12. Visual Alarm Light
13. External Hinged Door
Operations
Bay
1a.
Power pushbutton
1b. Transmitter Disable Button
1c. Transmitter Test
2. Sensor One and Two alarm level
adjustments
3. Sensor Calibration trimpots
4. Low/High alarm adjust pushbuttons
5. Service Bay Hinged Inner Door
|
|
|
|
Detector:
|
Independent
Wireless Sub-Site Control Monitor
|
|
Power:
12 V, 3.4
amp hr. rechargeable battery
|
| Charge
Life: |
Two
Toxic/Oxygen Sensors: 40 days normal operation
Two Combustible Sensors: 48 hours normal operation |
| Recharge
Via: |
Continuous:
Solar; 110/230 VAC or 24 VDC line power
Intermittent: Bench Charges; 110/230 VAC or 24 VDC |
| Battery
Back-up: |
Provided
- Dependent on power draw of interfaces |
| Fuses: |
One
(1) 750 mA surface mount (spare included) |
|
Signal
Transmission:
|
|
Signal
Output:
|
Discretely
coded radio signal to Controller
|
|
Frequency:
|
27.145
MHz
|
|
Range:
|
Up
to 4.0 miles (6.5 km)
|
|
Environmental:
|
|
Humidity:
|
5
to 99% non-condensing
|
|
Temperature:
|
Operating
Range: see Sensor specifications
|
|
Rating:
|
Enclosure:
Nema 3R
|
|
Physical:
|
|
Size:
|
4
x 6 x 10 in. (10 x 15.25 x 25.4 cm)
|
|
Weight:
|
11
lb. 6 oz. (5.15 kg)
|
|
Enclosure:
|
Rugged,
self contained 16 gauge stainless steel RFI/EMI
shielded c/w built-in carrying handle and mounting
flanges
|
| Outer
Door: |
Hinged
removable access door to operations bay |
| Control
Door: |
Hinged
removable access door to service bay |
| Controls:
Three |
Power:
ON/OFF pushbutton
Transmitter:
Disable pushbutton
Transmitter: Test pushbutton
Alarm Set: (LOW/HIGH) pushbuttons |
| Security: |
Key
lock access |
|
Alarms: Transmitted
to the Controller, activate option port interfaces
|
|
Audible:
|
Built-in
oscillating, 85 dB at 3 ft (1 m)
|
|
Visual:
|
Flashing
large red LED
Flashing "DANGER" icon on LCD
|
|
Gas
Alarms:
|
Two
Levels (Low/High) - Field programmable
|
|
Other:
|
Low
Battery; Sensor and Sensor Cable integrity
|
|
Display:
|
| LCDs: |
Two:
Alphanumeric Status-at-a-Glance readouts |
| Gas
Readouts: |
Continuous
LCD readouts for each sensor (ppm or %) |
| Status
Advice: |
Alarm
Level; Sensor Signal Status; Battery Level;
Transmitter |
| Ports: Plug-in
rugged mil-style c/w weather-tight covers |
| Sensor
Ports: |
RS-W2000:
Two (2) ports for Remote Gas Sensors |
| Charger
Port: |
One
(1) port accepts BW Solar Panels, Line & Bench
Chargers |
| Option
Ports: |
Two
(2) ports accept System options (Alarms, Relays, etc.) |
| Antenna
Port: |
One
(1) TNC connector |
| Ratings
and Certifications: |
| cCSAus |
Class
I, Div. 1, Groups C, D
Class II, Div. 1, Group G |
| Warranty |
2
Years non-prorated including sensors |
|
|
Due to on-going product
improvements specifications are subject to change without
notice.
|
|
|
|
Order
Info: Rig Rat II
Detectors are equipped with Radio Transmitter, RR-AR20 mid
range TNC Antenna, Battery Back-up, Local Audible/Visual
Alarms, two Remote Sensor ports, two Option Ports and
Power Supply Port. Included at the time of order are the
required remote sensor cables. Specify UC2-S010 (10 ft.; 3.1
m) or UC2-S003 (3 ft.; 0.9 m) for Tripod Mount.
| Order
# |
Description |
| RS-R2000 |
Rig
Rat II Gas Detector c/w two gas sensor ports |
| RS-W2000 |
Rig
Rat II Wind Detector. The Metrological Detector monitors
wind speed and direction and comes complete with
Propeller, Compass and Relay. Note: Gas Sensors are not
applicable.
See Rig Rat II Wind Detector. |
| Note: